CeilAir CW series Manuel de l'opérateur Page 38

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 60
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 37
(©July, 2008)
CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
3.0 Start-Up / Commissioning
3.1 Operation
For new installations, ensure the unit is ready to
operate by going through the completed installation
checklist provided with the unit, prior to start-up.
NOTE
Warranty Registration and Start-Up Checklist
should be completed during start-up and sent to
SATS. This checklist should be used as a guide-
line for items that need to be checked during
start-up.
Start-up must be performed by a journeyman, refrig-
eration mechanic or an air conditioning technician.
3.2 Step by Step Start-Up Instructions
CAUTION
For air-cooled outdoor condensers, apply power
to condenser eight hours before operating sys-
tem. This time is required to allow liquid refrig-
erant to be driven out of the compressor. The
compressor crank case heater is energized as
long as power is applied to the unit.
1. Replace all equipment, access panels and ceiling
panels removed prior to performing start-up
checks.
2. Apply power to start the
CeilAiR
OHS system at
the service disconnect switch, then turn the A/C
system on at the controller.
NOTE
The compressor may have a time delay on start-up.
3. Ensure that all blowers and fans are rotating freely
and without any unusual noise.
Water/Glycol-cooled units have a head pressure
water regulating valve that has been factory set.
A valve adjustment may be required based on
water temperatures or water/glycol flow condi-
tions at your site. (Refer to System Settings and
Adjustments.)
If you have selected a dual circuit unit, both re-
frigeration circuits must be tested at start-up.
There are several ways to force the second cir-
cuit into operation. If a microprocessor control-
ler was purchased it allows the unit to be placed
in a manual mode, refer to the separate Control-
ler Operations Manual sent with your unit.
4. Test cooling operation by setting the temperature
setpoint below the actual room temperature. The
compressor should come on and the discharge air
should feel cooler than the return air.
5. Test heating operation by setting the temperature
setpoint above the actual room temperature. The
source of heat should be energized to increase
discharge air temperature.
6. Test humidification operation by creating a
demand for humidification. Use an amp meter to
determine current draw of the humidifier. Visually
check for vapor leaving the steam head or feel if
the cylinder is warm to verify if the humidifier is
operational. In all cases, 1 to 6 hours might be
required to see a desired level or rise in humidity
in the conditioned space. Once room conditions
have been programmed or set, a repeat visit to the
conditioned space may be required to ensure the
humidifier is meeting the room’s requirements.
7. Test dehumidification operation by creating a
demand for dehumidification. If necessary, set the
dehumidification setpoint 10% below actual room
conditions, (the set point may already be below
actual room conditions, especially at start-up).
The chilled water valve should open to begin the
dehumidification process. While in this mode,
room temperature may decrease and the reheat
function may activate. As conditions in the room
change, you may have to readjust the setpoint as
you check operation. An adequate heat load
within the space is required.
8. For Electric Reheat, use an amp meter on the
heater circuit to determine if the heater is opera-
tional. For Hot Water Reheat, ensure the control
signal has energized the control valve and the
temperature of the water has decreased as it
passes through the unit. In all cases, 1 to 6 hours
might be required to see a desired level or
decrease in humidity in the conditioned space.
Once room conditions have been programmed or
set, a repeat visit to the conditioned space may
be required to ensure the dehumidification mode
is meeting the room’s requirements
.
3-1
Vue de la page 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 59 60

Commentaires sur ces manuels

Pas de commentaire