CeilAir CW series Manuel de l'opérateur Page 15

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 60
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 14
(©July, 2008)
CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
2-4
horizontally for ease of making wire connections. Each
transformer has keyhole mounting slots for mounting
with bolts to desired surface (wall, floor or other
structure capable of supporting its weight).
2.4.4.2 Condensate Pump (Field Installed)
The condensate pump should be as near to the air
conditioning system as possible. The inlet holes in the
pump must be below the lowest part of drain from unit.
The pump has two mounting supports so it can be
hung on an adjacent wall. Ensure that the pump is
level for proper operation.
2.4.4.3 Non-Fused Service Switch
The non-fused service switch is used to disconnect
main power and isolate the unit during maintenance and
service. The switch has a lockable handle to lock power
out during maintenance periods. The case has a top
keyhole slotting mount and two holes in each bottom
corner for mounting. The hardware for mounting is field
supplied and varies with size of switch and location.
The non-fused service switch can be mounted near the
unit or in a central location. The non-fused service
switches are rated for indoor or outdoor use. Ensure
that the proper type for your application is used.
NOTE
Refer to local and national electrical codes for
mounting location.
2.4.5 Remote Sensors
The remote temperature sensor or the temperature/
humidity (T/H) sensor must be located so that it will
properly sense the temperature and/or humidity
conditions to be controlled. The sensor should not be
mounted near a doorway or an area where it would be
exposed to direct sunlight. When locating the sensor,
consider the length of wire to be used. As an option, a
75 foot or 150 foot long cable may be provided by
SATS. Refer to the applicable section that follows to
mount the sensor. For unit wiring details, refer to
Section 2.7, Utility Connections and to the electrical
diagrams provided with the unit.
2.4.5.1 Remote Temperature Sensor
NOTE
The remote temperature sensor has a maximum
range of 300 feet.
1. Open the sensor case by depressing the button on
the bottom edge of the case until the latch releases.
2. Remove the cover by pulling it out and up at the
bottom.
3. Remove the circuit board from the base by pulling
back the latch that holds it at the center bottom.
4. Use the base as a template to mark the mounting
holes location on the wall.
5. Using a ¼ inch drill, drill the holes and insert the
provided wall anchors.
6. Run the wires coming out of the wall through the
opening in the base, then secure the base with the
screws provided.
7. Snap the circuit board back into the base. Ensure
that the latch holds the board properly and that the
sensor element is positioned under the holes in
the cover but not touching the cover or base.
8. Make the wiring connections.
9. Replace the cover.
2.4.5.2 Remote Temperature/Humidity Sensor
1. Using a flat head screwdriver, remove the cover
plate from the base of the sensor.
2. Place the base temporarily over the wire hole
opening in the wall. Level the base and mark the
mounting hole locations through the two slots.
3. Drill the mounting holes and insert the provided
wall anchors.
4. Run the wires coming out of the wall through the
opening in the base, then secure the base with the
screws provided.
5. Make the wiring connections.
6. Replace the cover plate on the base.
CAUTION
Take care not damage the exposed tempera-
ture/humidity sensors on the PC board while
screwing in the cover fastening screw. The sen-
sors can be damaged if handled improperly.
2.4.5.3 Remote Water Detector
The remote water detector is normally placed in an
auxiliary drain pan located under the
unit. It may be attached using double
sided tape or with the mounting holes
provided in the flanges (one on each
side). Once it’s in place, loosen the
screws provided on the mounting legs
to adjust the height of the sensing probes.
Vue de la page 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 59 60

Commentaires sur ces manuels

Pas de commentaire